+44 (0) 20 8405 6789
or email: sales@etscablecomponents.com
52 kV 52TTGE1 – 52TTGE1.400i
HEAT-SHRINK MV OUTDOOR TERMINATION FOR SINGLE CORE POLYMERIC CABLES WITH Cu WIRE SCREEN
Up to 26/42 (52) kV
APPLICATION
The “52TTGE1” terminations are designed for single core polymeric cables.
TECHNICAL FEATURES
A stress control patch is applied at the screen cut of the termination and helps to control the field together with stress control tubing.
Semiconductive tubing creates a bridge for leakage currents placed onto and covering the screen wires or earth braid.
Another layer of stress control mastic covers the top end of the semiconductive tubing.
Red anti-tracking mastic is wrapped onto the top end of the tubing.
The lug and cable outer sheath is sealed with anti-tracking mastic.
Heavy wall anti-tracking tube and anti-tracking rain sheds complete the termination.
A solderless roll force spring and an earthing braid are included in the kit (type Ai).
The design accommodates various conductor lugs.
MC types are supplied with “GPH” mechanical conductor lugs.
For cable with Al foil screen please ask to our sales representative.
Um kV | Section range (mm²) | DOI insulation (mm) | DOE Outer Sheath | L (mm) | 52 kV | 185-400 | 32-46 | 36-50 | 900 |